Engineering and Industrial Solutions

Loading

Insulated and non-insulated air Conductors

Description

OAC2X, ACSR-XLPE (ENG)

Type: OL-AL conductor with cross-linked polyethylene insulation, for 12/20 kV overhead power lines.
Internal symbol: OAC2X
International symbol: ACSR-XLPE (DIN 48204).
Standard: SF 2/1998, SFS 5791.
Field of use: For medium voltage electrical networks, where it is necessary to reduce the distance between the phases and where it is desired to eliminate the defects due to the accidental fall of vegetation on the networks.
construction:
Conductor pairs: aluminum wires, twisted concentrically around a galvanized steel core.
Insulation: black crosslinked polyethylene.
Technical data:
Minimum installation temperature: -20 ° C, maximum permissible conductor temperature: 90 ° C, rated voltage: 12/20 (24) kV, minimum installation radius: 15x cable diameter.

Technical parameters:

SectionExternal diameterInsulation thicknessTotal massBreaking resistanceResistance at 20 °C
(mm2)(mm)(mm)(kg/km)(kN)(Ohm/km)
Alum/OţelNom/max
35/612,5/14,22.521512.40.832
50/813,9/15,82.528016.80.595
70/1215,5/17,72.537523.40.422
95/1517,7/20,02.547033.70.321
120/2119,3/21,82.562545.90.235
150/2520,7/23,62.571553.70.194

OL-AL (ENG)

Type: aluminum rope conductor, with galvanized steel core.
Internal symbol: OL-AL
International symbol: ASCR (DIN 48204).
Standard: SF 2/1998, SFS 5791.
Field of use: for the transport of electricity in medium voltage networks.
construction:
Conductor: aluminum wires, twisted concentrically around a core made of galvanized steel.

Technical parameters:

SectionExternal diameterConstructionTotal massBreaking resistanceResistance at
20 °C
(mm2)(mm)(N/mm)(kg/km)(kN)(Ohm/km)
Alum/SteelAlumSteel
16/2,55,46/1,801/1,80625.951,8780
25/46,86/2,251/2,25979.201,2002
35/68,16/2,701/2,7014012.650,8352
44/3211,214/2,007/2,4037245.000,6573
50/89,66/3,201/3,2019617.100,5946
70/1211,726/1,857/1,4428426.800,4130
95/1513,426/2,17/1,6536633.400,3210
95/5516,012/3,207/3,2071279.350,2992
105/7517,514/3,1019/2,25891104.850,2735
120/2115,726/2,457/1,950245.440,2374
125/3016,330/2,337/2,3359157600,2364
150/2517,126/2,707/2,1060555.250,2259
170/4018,930/2,707/2,7079476750,1939
185/3219,226/3,007/2,4075766.200,1682
210/5021,030/3,007/3,0098193.900,1571
230/3021,024/3,507/2,3387773.100,1362
240/4021,926/3,457/2,6897886.400,1349
265/3522,424/3,447/2,49100283.050,1188
300/5024,526/3,867/3,001236107.000,1094
305/4024,154/2,687/2,68116099.400,09487
340/3025,048/3,007/2,33118092.900,09490
380/5027,054/3,007/3,001453123.100,08509
385/3526,748/3,207/2,491344104.800,07573
435/5528,854/3,207/3,201653136.450,07478
450/7529,2563/319/2,251820162.340,0655
490/6530,654/3,407/3,401866153.100,05896
495/3529,945/3,747/2,491646121.800,05846
510/4530,748/3,687/2,871778136.650,06555
550/7032,454/3,607/3,602092170.600,05259
560/5032,248/3,867/3,001954148.950,05140
570/4032,248/4,007/2,681888139.000,05108
632/4534,045/4,237/2,872118155.800,04569
680/8536,054/4,0019/2,402570210.400,04260

TYIR (ENG)

Type: twisted aluminum conductors, insulated with PVC.
International symbol: TYIR (SP 5201: 1993).
Rated voltage: 0.6 / 1 (1.2) kV.
Field of use: power supply of various objectives, its transport and distribution.
construction:
Conductor: single- or multifilament aluminum insulated with PVC (on request with XLPE insulation) and zero carrier made of OL-AL 50/8 insulated with PVC (on request with XLPE insulation).
Ambient temperature: posed: from -30 ° Cla + 70 ° C, to installation from +5 ° C.

Technical parameters:

SectionTotal massAluminum massEquivalent external diameter
(mm2)(kg/km)(kg/km)(mm)
TYIR 10+161647516.0
TYIR 16+2522511819.0
TYIR 2+101365814.4
TYIR 2+161939217.4
TYIR 2+2525814520.0
TYIR 3×16+2541821018.0
TYIR 3×25+1648326421.0
TYIR 3×3549630423.9
TYIR 4×1072711617.4
TYIR 4×1638618521.0
TYIR 50OL-AL 1×1637017621.0
TYIR 50OL-AL 2×1645522222.0
TYIR 50OL-AL 3×1654027122.0
TYIR 50OL-AL 4×1663031427.0
TYIR 50OL-AL 1×2541020423.0
TYIR 50OL-AL 2×2554027724.0
TYIR 50OL-AL 3×2567534925.0
TYIR 50OL-AL 1×3545023324.0
TYIR 50OL-AL 2×3561533525.0
TYIR 50OL-AL 3×3578043627.0
TYIR 50OL-AL 1×5050027725.0
TYIR 50OL-AL 2×5072042227.0
TYIR 50OL-AL 3×5094056730.0
TYIR 50OL-AL 1×7057033527.0
TYIR 50OL-AL 2×7085553828.0
TYIR 50OL-AL 3×70114074133.0
TYIR 50OL-AL 3×95148096038.0
SectionTotal massAluminum massEquivalent external diameter
(mm2)(kg/km)(kg/km)(mm)
TYIR 50OL-AL 3×16+2×1671536417.0
TYIR 50OL-AL 3×16+3×1680541017.0
TYIR 50OL-AL 1×25+1×1650025023.0
TYIR 50OL-AL 1×25+3×1667534323.0
TYIR 50OL-AL 3×25+1×1676039626.0
TYIR 50OL-AL 3×25+2×1685044226.0
TYIR 50OL-AL 3×25+3×1693548826.0
TYIR 50OL-AL 3×25+2×2593549426.0
TYIR 50OL-AL 1×35+1×1653527924.0
TYIR 50OL-AL 1×35+1×2558030624.0
TYIR 50OL-AL 2×35+2×1670042725.0
TYIR 50OL-AL 3×35+1×1687048230.0
TYIR 50OL-AL 1×50+1×1659032325.0
TYIR 50OL-AL 1×50+1×3567037825.0
TYIR 50OL-AL 2×50+1×3589052327.0
TYIR 50OL-AL 3×50+1×16103061334.0
TYIR 50OL-AL 3×70+1×16123078738.0
TYIR 50OL-AL 3×35+2×1695552730.0
TYIR 50OL-AL 3×35+1×2591050930.0
TYIR 50OL-AL 3×35+3×25117565430.0
TYIR 50OL-AL 3×35+3×16104557630.0
TYIR 50OL-AL 3×35+1×3595053830.0
TYIR 50OL-AL 3×50+2×16112065934.0
TYIR 50OL-AL 3×70+2×16131583338.0
TYIR 50OL-AL 3×50+3×16120570634.0
TYIR 50OL-AL 3×50+1×25107564034.0
TYIR 50OL-AL 3×50+2×25120571334.0
TYIR 50OL-AL 3×50+3×25133578634.0
TYIR 50OL-AL 3×50+1×35111066934.0
TYIR 50OL-AL 3×50+3×501605100234.0
TYIR 50OL-AL 3×70+3×16140088038.0
TYIR 50OL-AL 3×70+1×25127081438.0
TYIR 50OL-AL 3×70+2×251400887173.0
TYIR 50OL-AL 3×70+3×251535960173.0
TYIR 50OL-AL 3×50+3×351440873140.0
TYIR 50OL-AL 3×70+1×351305863173.0
TYIR 50OL-AL 3×70+2×351475945173.0
TYIR 50OL-AL 3×70+3×3516401047173.0
TYIR 50OL-AL 3×70+3×5018001176173.0
TYIR 50OL-AL 3×95+2×1615651052210.0
TYIR 50OL-AL 3×95+2×2517401106210.0
TYIR 50OL-AL 3×95+3×2518701179210.0
TYIR 50OL-AL 3×95+2×3518101161210.0
TYIR 50OL-AL 3×95+3×3519751263210.0
TYIR 50OL-AL 3×95+1×5017001103210.0