Medium voltage Cables

Description

 

N2XS2Y, 2XS2Y (ENG)

Type: copper cable, medium voltage, single phase, polyethylene (PE) sheath.
International symbol: N2XS2Y (VDE 0276).
Rated voltage: 6/10 kV … 20/36 kV.
Field of use: in transformer stations, industrial areas, for powering objectives.
construction:
Conductor: copper mutifilation, twisted and compacted, semiconductor layer no.1.
Insulation: made of cross-linked polyethylene, semiconductor layer no.2.
Shielding: copper wire, copper strip, separating layer.
Sheath: black polyethylene.
Ambient temperature: -20 ° C to +80 ° C, maximum allowable temperature: +90 ° C, maximum short circuit temperature: +250 ° C.

Technical parameters:

Section External diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
N2XS2Y 6/10 kV
1×50 RM/16 27,7 662 1078 220 234
1×70 RM/16 29,2 854 1298 269 292
1×95 RM/16 30,9 1094 1566 321 354
1×120 RM/16 32,3 1334 1823 364 407
1×150 RM/25 33,8 1723 2211 405 460
1×185 RM/25 35,4 2059 2565 457 527
1×240 RM/25 37,6 2587 3113 528 621
1×300 RM/25 39,8 3163 3708 593 709
1×400 RM/35 43,3 4234 4801 665 815
1×500 RM/35 46 5194 5768 739 921
Section External diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
N2XS2Y 12/20 kV
1×50 RM/16 31,9 662 1244 223 238
1×70 RM/16 33,4 854 1473 273 296
1×95 RM/16 35,1 1094 1753 325 358
1×120 RM/16 36,5 1334 2019 368 412
1×150 RM/25 38 1723 2414 410 466
1×185 RM/25 39,6 2059 2779 463 532
1×240 RM/25 41,8 2587 3340 543 627
1×300 RM/25 44 3163 3948 601 715
1×400 RM/35 47,5 4234 5059 674 819
1×500 RM/35 50,2 5194 6044 750 927
Section External diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
N2XS2Y 18/30 kV
1×50 RM/16 36,9 662 1476 226 241
1×70 RM/16 38,4 854 1715 276 299
1×95 RM/16 40,1 1094 2008 329 362
1×120 RM/16 41,5 1334 2282 373 416
1×150 RM/25 43 1723 2689 415 469
1×185 RM/25 44,6 2059 3066 468 536
1×240 RM/25 46,8 2587 3642 541 630
1×300 RM/25 49 3163 4268 608 717
1×400 RM/35 52,7 4234 5401 684 823
1×500 RM/35 55,4 5194 6529 762 929
Section External diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
2XS2Y 20/36 kV
1×50 RM/16 38,5 662 1558 226 241
1×70 RM/16 40 584 1801 276 299
1×95 RM/16 41,7 1094 2097 329 362
1×120 RM/16 43,1 1334 2374 373 416
1×150 RM/25 44,6 1723 2785 415 469
1×185 RM/25 46,2 2059 3166 468 536
1×240 RM/25 48,4 2587 3748 541 630
1×300 RM/25 50,6 3163 4376 608 717
1×400 RM/35 54,3 4234 5551 684 823
1×500 RM/35 57,2 5194 6563 762 929

 

NYSEY, N2XSEY (ENG)

Type: three-phase copper cable, shielded on each phase separately and with common PVC sheath.
International symbol: NYSEY, N2XSEY (VDE 0271, 0273).
Rated voltage: 6/10 kV.
Field of use: in transformer stations, industrial areas, for powering objectives.
construction:
Conductor: copper mutifilation, twisted and compacted, semiconductor layer no.1.
Insulation: made of cross-linked polyethylene or PVC, semiconductor layer no.2.
Shielding: copper wire, copper strip, barrier against water penetration.
Sheath: made of red PVC.
Ambient temperature: -5 ° C to +70 ° C, maximum permissible temperature: +70 ° C (PVC insulation), +90 ° C (polyethylene insulation), maximum short circuit temperature for 5 sec: +160 ° C (PVC insulation), +160 ° C (polyethylene insulation).

Technical parameters:

Section External diameter min. External diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (mm) (kg/km) (kg/km) (A) (A)
NYSEY 6/10 kV
3×25 RM/16 41 52 960 2890 133 114
3×35 RM/16 43 54 1260 3330 160 138
3×50 RM/16 46 57 1690 3890 189 165
3×70 RM/16 49 60 2290 4800 230 204
3×95 RM/16 53 65 3040 5970 275 247
3×120 RM/16 57 69 3790 6960 312 284
3×150 RM/25 60 72 4795 8140 350 322
3×185 RM/25 64 77 5845 9410 394 367
3×240 RM/25 69 82 7495 11730 455 430
N2XSEY 6/10 kV
3×35 RM/16 46 49 1260 2380 178 173
3×50 RM/16 49 52 1690 2600 210 206
3×70 RM/16 52 56 2290 3350 256 257
3×95 RM/16 56 60 3040 4200 307 313
3×120 RM/16 60 64 3790 5050 349 360
3×150 RM/25 65 68 4795 6000 392 410
3×185 RM/25 67 70 5845 7200 443 469
3×240 RM/25 72 76 7495 9000 513 553

 

N2XS(F)2Y, 2XS(F)2Y (ENG)

Type: single voltage copper cable, single phase, polyethylene (PE) sheath and barrier against water penetration.
International symbol: N2XS (FL) 2Y (VDE 0276).
Rated voltage: 6/10 kV … 20/36 kV.
Field of use: in transformer stations, industrial areas, for powering objectives.
construction:
Conductor: copper mutifilation, twisted and compacted, semiconductor layer no.1.
Insulation: made of cross-linked polyethylene, semiconductor layer no.2.
Shielding: copper wire, copper strip, barrier against water penetration.
Sheath: black polyethylene.
Ambient temperature: -20 ° C to +80 ° C, maximum allowable temperature: +90 ° C, maximum short circuit temperature: +250 ° C.

Technical parameters:

Section External diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
N2XS(F)2Y 6/10 kV
1×50 RM/16 28,6 662 1085 220 234
1×70 RM/16 30,1 854 1305 269 292
1×95 RM/16 31,8 1094 1573 321 354
1×120 RM/16 33,2 1334 1830 364 407
1×150 RM/25 34,7 1723 2217 405 460
1×185 RM/25 36,3 2059 2573 457 527
1×240 RM/25 38,5 2587 3120 528 621
1×300 RM/25 40,7 3163 3716 593 709
1×400 RM/35 44,2 4234 4807 665 815
1×500 RM/35 46,9 5194 5775 739 921
Section External diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
N2XS(F)2Y 12/20 kV
1×50 RM/16 32,8 662 1252 223 238
1×70 RM/16 34,3 854 1480 273 296
1×95 RM/16 36 1094 1761 325 358
1×120 RM/16 37,4 1334 2024 368 412
1×150 RM/25 38,9 1723 2421 410 466
1×185 RM/25 40,5 2059 2786 463 532
1×240 RM/25 42,7 2587 3346 534 627
1×300 RM/25 44,9 3163 3955 601 715
1×400 RM/35 48,4 4234 5066 674 816
1×500 RM/35 51,1 5194 6051 750 927
Section External diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
N2XS(F)2Y 18/30 kV
1×50 RM/16 37,8 662 1482 226 241
1×70 RM/16 39,3 854 1722 276 299
1×95 RM/16 41 1094 2014 329 362
1×120 RM/16 42,4 1334 2288 373 416
1×150 RM/25 43,9 1723 2696 415 469
1×185 RM/25 45,5 2059 3073 468 536
1×240 RM/25 47,7 2587 3649 541 630
1×300 RM/25 49,9 3163 4274 608 717
1×400 RM/35 53,4 4234 5407 684 823
1×500 RM/35 56,3 5194 6429 762 929
Section External diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
2XS(F)2Y 20/36 kV
1×50 RM/16 39,4 662 1564 226 241
1×70 RM/16 40,9 854 1807 276 299
1×95 RM/16 42,6 1094 2103 329 362
1×120 RM/16 44 1334 2381 373 416
1×150 RM/25 45,5 1723 2792 415 469
1×185 RM/25 47,1 2059 3173 468 536
1×240 RM/25 49,3 2587 3754 541 630
1×300 RM/25 51,5 3163 4383 608 717
1×400 RM/35 55,2 4234 5540 684 823
1×500 RM/35 58,1 5194 6569 762 929

 

 

N2XS(FL)2Y, 2XS(FL)2Y (ENG)

Type: medium voltage copper cable, single phase, polyethylene (PE) sheath and double barrier, longitudinal and transverse, against water penetration.
International symbol: N2XS (FL) 2Y (VDE 0276).
Rated voltage: 6/10 kV … 20/36 kV.
Field of use: in transformer stations, industrial areas, for powering objectives.
construction:
Conductor: copper mutifilation, twisted and compacted, semiconductor layer no.1.
Insulation: made of cross-linked polyethylene, semiconductor layer no.2.
Filling: extruded XLPE cross-linked polyethylene.
Shielding: copper wire, copper strip.
Barriers: longitudinal and transverse against water penetration.
Sheath: black polyethylene.
Ambient temperature: -20 ° C to +80 ° C, maximum allowable temperature: +90 ° C, maximum short circuit temperature: +250 ° C.

Technical parameters:

Section External diameter max. Conductor diameter max. Aprox. total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (mm) (kg/km) (A) (A)
N2XS(FL)2Y 6/10 kV
1×50 RM/16 24,5 8,2 890 231 260
1×70 RM/16 26,0 9,8 1120 283 326
1×95 RM/16 28,0 11,4 1390 340 398
1×120 RM/16 29,5 12,9 1650 386 459
1×150 RM/25 30,5 14,2 1920 431 520
1×185 RM/25 32,5 15,8 2330 489 600
1×240 RM/25 35,5 18,2 2880 565 705
1×300 RM/25 37,5 20,3 3510 635 810
1×400 RM/35 40,5 23,5 4310 720 935
1×500 RM/35 44,0 26,3 5430 810 1080
N2XS(FL)2Y 12/20 kV
1×50 RM/16 29,0 8,2 1080 224 255
1×70 RM/16 30,0 9,8 1330 274 320
1×95 RM/16 32,0 11,4 1640 328 390
1×120 RM/16 34,0 12,9 1920 373 450
1×150 RM/25 35,5 14,2 2200 416 510
1×185 RM/25 37,5 15,8 2580 471 585
1×240 RM/25 39,5 18,2 3160 544 690
1×300 RM/25 42,5 20,3 3800 611 790
1×400 RM/35 45,5 23,5 4660 688 910
1×500 RM/35 49,5 26,3 5810 776 1050

 

 

N2XSY, 2XSY (ENG)

Type: medium voltage copper cable, single phase, with PVC sheath.
International symbol: N2XSY (VDE 0276).
Rated voltage: 6/10 kV … 20/36 kV.
Field of use: in electricity supply stations, in indoor spaces, in cable ducts, outdoors, in underground lines, in water, transformer stations, industrial areas for powering objectives. The screen limits the action of electromagnetic fields; the same effect is given by the semiconductor layers located at the level of the insulation.
construction:
Conductor: copper mutifilation, twisted and compacted, semiconductor layer no.1.
Insulation: made of cross-linked polyethylene, semiconductor layer no.2.
Shielding: copper wire, copper strip, separating layer.
Sheath: red PVC.
Ambient temperature: -5 ° C to +70 ° C.

Technical parameters:

Section External diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
N2XSY 6/10 kV
1×50 RM/16 27,7 662 1187 220 234
1×70 RM/16 29,2 854 1413 269 292
1×95 RM/16 30,9 1094 1689 321 354
1×120 RM/16 32,3 1334 1952 364 407
1×150 RM/25 33,8 1723 2346 405 460
1×185 RM/25 35,4 2059 2707 457 527
1×240 RM/25 37,6 2587 3265 528 621
1×300 RM/25 39,8 3163 3870 593 709
1×400 RM/35 43,3 4234 4977 665 815
1×500 RM/35 46 5194 5956 739 921
Section External diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
N2XSY 12/20 kV
1×50 RM/16 31,9 662 1371 223 238
1×70 RM/16 33,4 854 1606 273 296
1×95 RM/16 35,1 1094 1893 325 358
1×120 RM/16 36,5 1334 2166 368 412
1×150 RM/25 38 1723 2566 410 466
1×185 RM/25 39,6 2059 2939 463 532
1×240 RM/25 41,8 2587 3510 543 627
1×300 RM/25 44 3163 4128 601 715
1×400 RM/35 47,5 4234 5255 674 819
1×500 RM/35 50,2 5194 6251 750 927
Section External diameter max. Copper mass total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
N2XSY 18/30 kV
1×50 RM/16 36,9 662 1625 226 241
1×70 RM/16 38,4 854 1871 276 299
1×95 RM/16 40,1 1094 2170 329 362
1×120 RM/16 41,5 1334 2451 373 416
1×150 RM/25 43 1723 2865 415 469
1×185 RM/25 44,6 2059 3248 468 536
1×240 RM/25 46,8 2587 3834 541 630
1×300 RM/25 49 3163 4469 608 717
1×400 RM/35 52,7 4234 5618 684 823
1×500 RM/35 55,4 5194 6660 762 929
Section Wzternal diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
2XSY 20/36 kV
1×50 RM/16 38,5 662 1714 226 241
1×70 RM/16 40 584 1963 276 299
1×95 RM/16 41,7 1094 2267 329 362
1×120 RM/16 43,1 1334 2550 373 416
1×150 RM/25 44,6 1723 2967 415 469
1×185 RM/25 46,2 2059 3355 468 536
1×240 RM/25 48,4 2587 3947 541 630
1×300 RM/25 50,6 3163 4585 608 717
1×400 RM/35 54,3 4234 5767 684 823
1×500 RM/35 57,2 5194 6817 762 929

NA2XS2Y, A2XS2Y (ENG)

Type: medium voltage aluminum cable, single phase, polyethylene (PE) sheath.
International symbol: NA2XS2Y (VDE 0276).
Rated voltage: 6/10 kV … 20/36 kV.
Field of use: in transformer stations, industrial areas, for powering objectives.
construction:
Conductor: aluminum mutifilation, twisted and compacted, semiconductor layer no.1.
Insulation: made of cross-linked polyethylene, semiconductor layer no.2.
Shielding: copper wire, copper strip, separating layer.
Sheath: black polyethylene.
Ambient temperature: -20 ° C to +80 ° C, maximum allowable temperature: +90 ° C, maximum short circuit temperature: +250 ° C.

Technical parameters:

Section External diameter max. Copper mass Aluminum mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (kg/km) (A) (A)
NA2XS2Y 6/10 kV
1×50 RM/16 27,7 182 145 765 171 181
1×70 RM/16 29,2 182 203 589 209 226
1×95 RM/16 30,9 182 276 971 249 275
1×120 RM/16 32,3 182 348 1071 283 317
1×150 RM/25 33,8 283 435 1272 316 359
1×185 RM/25 35,4 283 537 1407 358 412
1×240 RM/25 37,6 283 696 1610 416 489
1×300 RM/25 39,8 283 870 1830 469 559
1×400 RM/25 43,3 394 1160 2297 532 651
1×500 RM/25 46 394 1450 2637 599 744
Section External diameter max. Copper mass Aluminum mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (kg/km) (A) (A)
NA2XS2Y 12/20 kV
1×50 RM/16 31,9 182 145 931 173 184
1×70 RM/16 33,4 182 203 1034 211 229
1×95 RM/16 35,1 182 276 1158 252 278
1×120 RM/16 36,5 182 348 1267 287 320
1×150 RM/25 38 283 435 1475 320 363
1×185 RM/25 39,6 283 537 1621 362 415
1×240 RM/25 41,8 283 696 1837 421 493
1×300 RM/25 44 283 870 2070 474 563
1×400 RM/25 47,5 394 1160 2555 538 652
1×500 RM/25 50,2 394 1450 2913 606 746
Section External diameter max. Copper mass Aluminum mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (kg/km) (A) (A)
NA2XS2Y 18/30 kV
1×50 RM/16 36,9 182 145 1163 175 187
1×70 RM/16 38,4 182 203 1276 214 232
1×95 RM/16 40,1 182 276 1413 256 281
1×120 RM/16 41,5 182 348 1530 290 323
1×150 RM/25 43 283 435 1750 324 365
1×185 RM/25 44,6 283 537 1908 366 418
1×240 RM/25 46,8 283 696 2139 426 494
1×300 RM/25 49 283 870 2390 479 564
1×400 RM/25 52,7 394 1160 2897 545 654
1×500 RM/25 55,4 394 1450 3293 614 747
Sectiunea External diameter max. Copper mass Aluminum mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (kg/km) (A) (A)
A2XS2Y 20/36 kV
1×50 RM/16 38,5 182 145 1245 175 187
1×70 RM/16 40 182 203 1362 214 232
1×95 RM/16 41,7 182 276 1502 256 281
1×120 RM/16 43,1 182 348 1622 290 323
1×150 RM/25 44,6 283 435 1846 324 365
1×185 RM/25 46,2 283 537 2008 366 418
1×240 RM/25 48,4 283 696 2245 426 494
1×300 RM/25 50,6 283 870 2498 479 564
1×400 RM/25 54,3 394 1160 3031 545 654
1×500 RM/25 57,2 394 1450 3432 614 747

NA2XS(F)2Y, A2XS(F)2Y (ENG)

Type: medium voltage aluminum cable, single- or three-phase, polyethylene (PE) sheath and barrier against water penetration.
International symbol: NA2XS (F) 2Y (VDE 0276).
Rated voltage: 6/10 kV … 20/36 kV.
Field of use: in transformer stations, industrial areas, for powering objectives.
construction:
Conductor: aluminum mutifilation, twisted and compacted, semiconductor layer no.1.
Insulation: made of cross-linked polyethylene, semiconductor layer no.2.
Shielding: copper wire, copper strip, barrier against water penetration.
Sheath: black polyethylene. Obtaining the three-phase cable is done by twisting three single-phase cables.
Ambient temperature: -20 ° C to +80 ° C, maximum allowable temperature: +90 ° C, maximum short circuit temperature: +250 ° C.

Technical parameters:

Section External diameter max. Copper mass Aluminum mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (kg/km) (A) (A)
NA2XS(F)2Y 6/10 kV
1×50 RM/16 28,6 182 145 772 171 181
1×70 RM/16 30,1 182 203 866 209 226
1×95 RM/16 31,8 182 276 978 249 275
1×120 RM/16 33,2 182 348 1078 283 317
1×150 RM/25 34,7 283 435 1278 316 359
1×185 RM/25 36,3 283 537 1415 358 412
1×240 RM/25 38,5 283 696 1617 416 489
1×300 RM/25 40,7 283 870 1838 469 559
1×400 RM/35 44,2 394 1160 2303 532 651
1×500 RM/35 46,9 394 1450 2644 599 744
3 x 1×95 RM/16 68,7 546 828 2964 249 275
3 x 1×120 RM/16 71,7 546 1044 3267 283 317
3 x 1×150 RM/25 75 849 1305 3873 316 359
3 x 1×185 RM/25 78,4 849 1611 4288 358 412
3 x 1×240 RM/25 83,2 849 2088 4900 416 489
3 x 1×300 RM/25 87,9 849 2610 5570 469 559
Section External diameter max. Copper mass aluminum mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (kg/km) (A) (A)
NA2XS(F)2Y 12/20 kV
1×50 RM/16 32,8 182 145 939 173 184
1×70 RM/16 34,3 182 203 1041 211 229
1×95 RM/16 36 182 276 1166 252 278
1×120 RM/16 37,4 182 348 1272 287 320
1×150 RM/25 38,9 283 435 1482 320 363
1×185 RM/25 40,5 283 537 1628 362 415
1×240 RM/25 42,7 283 696 1843 421 493
1×300 RM/25 44,9 283 870 2077 474 563
1×400 RM/35 48,4 394 1160 2562 538 652
1×500 RM/35 51,1 394 1450 2920 606 746
3 x 1×95 RM/16 77,8 546 828 3555 252 278
3 x 1×120 RM/16 80,8 546 1044 3855 287 320
3 x 1×150 RM/25 84 849 1305 4491 320 363
3 x 1×185 RM/25 87,5 849 1611 4933 362 415
3 x 1×240 RM/25 92,2 849 2088 5585 421 493
Section External diameter max. Copper mass Aluminum mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (kg/km) (A) (A)
NA2XS(F)2Y 18/30 kV
1×50 RM/16 37,8 182 145 1169 175 187
1×70 RM/16 39,3 182 203 1283 214 232
1×95 RM/16 41 182 276 1419 256 281
1×120 RM/16 42,4 182 348 1536 290 323
1×150 RM/25 43,9 283 435 1757 324 365
1×185 RM/25 45,5 283 537 1915 366 418
1×240 RM/25 47,7 283 696 2146 426 494
1×300 RM/25 49,9 283 870 2396 479 564
1×400 RM/35 53,4 394 1160 2903 545 654
1×500 RM/35 56,3 394 1450 3298 614 747
Section External diameter max. Copper mass Aluminum mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (kg/km) (A) (A)
NA2XS(F)2Y 20/36 kV
1×50 RM/16 39,4 182 145 1251 175 187
1×70 RM/16 40,9 182 203 1368 214 232
1×95 RM/16 42,6 182 276 1508 256 281
1×120 RM/16 44 182 348 1629 290 323
1×150 RM/25 45,5 283 435 1853 324 365
1×185 RM/25 47,1 283 537 2015 366 418
1×240 RM/25 49,3 283 696 2251 426 494
1×300 RM/25 51,5 283 870 2505 479 564
1×400 RM/35 55,2 394 1160 3036 545 654
1×500 RM/35 58,1 394 1450 3438 614 747

 

NA2XS(FL)2Y, A2XS(FL)2Y (ENG)

Type: medium voltage aluminum cable, single- or three-phase, polyethylene (PE) sheath with double barrier, longitudinal and transverse, against water penetration.
International symbol: NA2XS (FL) 2Y (VDE 0276-620).
Rated voltage: 6/10 kV … 20/36 kV.
Field of use: in transformer stations, industrial areas, for powering objectives.
construction:
Conductor: aluminum mutifilation, twisted and compacted, semiconductor layer no.1.
Insulation: made of cross-linked polyethylene, semiconductor layer no.2.
Filling: extruded XLPE cross-linked polyethylene.
Shielding: copper wire, copper strip, barrier against water penetration.
Barriers: longitudinal and transverse against water penetration.
Sheath: black polyethylene.
Ambient temperature: -20 ° C to +80 ° C, maximum allowable temperature: +90 ° C, maximum short circuit temperature: +250 ° C.

Technical parameters:

Section External diameter max. Conductor diameter max. Aprox. total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (mm) (kg/km) (A) (A)
NA2XS(FL)2Y 6/10 kV
1×50 RM/16 24,5 8,2 590 195 220
1×70 RM/16 26,0 9,8 690 237 276
1×95 RM/16 28,0 11,4 790 281 335
1×120 RM/16 29,5 12,9 900 319 386
1×150 RM/25 30,5 14,2 1000 351 435
1×185 RM/25 32,5 15,8 1220 394 497
1×240 RM/25 35,5 18,2 1430 453 586
1×300 RM/25 37,5 20,3 1660 506 668
1×400 RM/35 40,5 23,5 2060 560 760
1×500 RM/35 44,0 26,3 2450 627 868
NA2XS(FL)2Y 12/20 kV
1×50 RM/16 29,0 8,2 760 195 221
1×70 RM/16 30,0 9,8 860 238 275
1×95 RM/16 32,0 11,5 980 282 334
1×120 RM/16 34,0 12,9 1080 320 385
1×150 RM/25 35,0 14,5 1200 353 434
1×185 RM/25 37,5 15,8 1430 397 496
1×240 RM/25 39,5 18,2 1665 456 584
1×300 RM/25 42,5 20,3 1915 510 665
1×400 RM/35 46,0 23,5 2330 565 758
1×500 RM/35 49,5 26,5 2750 635 868

NA2XSY, A2XSY (ENG)

Type: medium voltage aluminum cable, single phase, PVC sheath.
International symbol: NA2XSY (VDE 0276).
Rated voltage: 6/10 kV … 20/36 kV.
Field of use: in electricity supply stations, in indoor spaces, in cable ducts, outdoors, in underground lines, in water, in transformer stations, industrial areas, for powering objectives.
construction:
Conductor: aluminum mutifilation, twisted and compacted, semiconductor layer no.1.
Insulation: made of cross-linked polyethylene, semiconductor layer no.2.
Shielding: copper wire, copper strip, separating layer.
Sheath: red PVC.
Ambient temperature: -5 ° C to +70 ° C.

Technical parameters:

Section External diameter max. Copper mass Aluminum mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (kg/km) (A) (A)
NA2XSY 6/10 kV
1×50 RM/16 27,7 182 145 874 171 181
1×70 RM/16 29,2 182 203 974 209 226
1×95 RM/16 30,9 182 276 1094 249 275
1×120 RM/16 32,3 182 348 1200 283 317
1×150 RM/25 33,8 283 435 1407 316 359
1×185 RM/25 35,4 283 537 1549 358 412
1×240 RM/25 37,6 283 696 1762 416 489
1×300 RM/25 39,8 283 870 1992 469 559
1×400 RM/35 43,3 394 1160 2473 532 651
1×500 RM/35 46 394 1450 2825 599 744
Section External diameter max. Copper mass Aluminum mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (kg/km) (A) (A)
NA2XSY 12/20 kV
1×50 RM/16 31,9 182 145 1058 173 184
1×70 RM/16 33,4 182 203 1167 211 229
1×95 RM/16 35,1 182 276 1298 252 278
1×120 RM/16 36,5 182 348 1414 287 320
1×150 RM/25 38 283 435 1629 320 363
1×185 RM/25 39,6 283 537 1781 362 415
1×240 RM/25 41,8 283 696 2007 421 493
1×300 RM/25 44 283 870 2250 474 563
1×400 RM/35 47,5 394 1160 2751 538 652
1×500 RM/35 50,2 394 1450 3120 606 746
Section External diameter max. Copper mass Aluminum mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (kg/km) (A) (A)
NA2XSY 18/30 kV
1×50 RM/16 36,9 182 145 1312 175 187
1×70 RM/16 38,4 182 203 1432 214 232
1×95 RM/16 40,1 182 276 1575 256 281
1×120 RM/16 41,5 182 348 1699 290 323
1×150 RM/25 43 283 435 1926 324 365
1×185 RM/25 44,6 283 537 2090 366 418
1×240 RM/25 46,8 283 696 2331 426 494
1×300 RM/25 49 283 870 2591 479 564
1×400 RM/35 52,7 394 1160 3138 545 654
1×500 RM/35 55,4 394 1450 3529 614 747
Section External diameter max. Copper mass Aluminum mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (kg/km) (A) (A)
A2XSY 20/36 kV
1×50 RM/16 38,5 182 145 1401 175 187
1×70 RM/16 40 182 203 1524 214 232
1×95 RM/16 41,7 182 276 1672 256 281
1×120 RM/16 43,1 182 348 1798 290 323
1×150 RM/25 44,6 283 435 2028 324 365
1×185 RM/25 46,2 283 537 2197 366 418
1×240 RM/25 48,4 283 696 2444 426 494
1×300 RM/25 50,6 283 870 2707 479 564
1×400 RM/35 54,3 394 1160 3263 545 654
1×500 RM/35 57,2 394 1450 3686 614 747